Behaviour FG_System Safety
Published from
_docs/reference/fg-system-safety.md— edit it there, not here. Changes made in the wiki are overwritten on the next sync.
Cell infrastructure: the enclosure, the six interlocked doors, the two emergency stops and the signal tower. It processes no parts. Written from the shipped ST; the PLC is master for behaviour.
Sources: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/01 FG_System/FG_System.TcPOU, Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/00 Machine/Machine.TcPOU.
FG_System publishes two facts about the machinery and applies no policy to them.
| Level | Owns | Members |
|---|---|---|
FG_System |
the facts |
GuardsSecure, EmergencyStopActive
|
Machine |
the policy |
SafetyOk, EnforceSafety
|
Only the machine owns the PackML mode, and an equipment module that knows what
ePMLUnitMode_Production implies has reached past its level. That is why the mode test lives in
Machine.SafetyOk and not here.
Both facts are property getters, computed on every read — never stored flags. Same rule the
transport stations follow for CanAccept and Occupied, for the same reason: a remembered readiness
flag maintained in one state is stale in all the others.
EmergencyStopActive := SS_EStop1.Active OR SS_EStop2.Active;
GuardsSecure := B_SafetyDoor11.Secure AND ... AND B_SafetyDoor23.Secure;
Secure is shut AND locked. Closed alone is not enough.
SafetyOk := NOT FG_System.EmergencyStopActive
AND ( (_CurrentMode <> ePMLUnitMode_Production) OR FG_System.GuardsSecure );
Mode is the gate, and the two inputs are gated differently on purpose:
| Input | Acts in | Why |
|---|---|---|
| Emergency stops | every mode | a mushroom is the one input that is never mode-dependent, and Manual is precisely the mode where somebody is inside the cell jogging a cylinder |
| Guard doors | Production only, every state | Maintenance and Manual ignore them — that is what those modes are for, and it is the only way into the cell, because the locks are commanded throughout Production |
Machine.EnforceSafety calls AbortImmediate() whenever SafetyOk is false, except in
Aborting, Aborted and Clearing:
| Excluded state | Why |
|---|---|
Aborting / Aborted
|
re-issuing AbortImmediate() every scan overwrites the command that would leave Aborted, so the machine could never recover. This is a deadlock, and the exclusion is the fix. |
Clearing |
we are in Clearing because safety broke. Aborting out of it makes clearing impossible. |
This is the path that disables FG_01's laser and retracts FG_04's press: the machine aborts, and the
base Aborting carries the abort down to every registered submodule.
_DoorsRequestedLocked := (_MachineMode = ePMLUnitMode_Production);
Sealed in Production, free in Maintenance and Manual. That is the whole rule.
It is what makes "closed and locked in every Production state" reachable at all: the locks are already commanded at power-up, long before any reset, so a reset never has to wait for them.
The consequence is deliberate: an operator in Production cannot open a door at all. Getting into the cell means selecting Maintenance or Manual, which drops every lock.
A door has 3 s (LockTime) to confirm its lock before raising its own fault 1.
The tower shows the MACHINE's state, not this module's. Machine.Execute deliberately does not
call SUPER^.Execute(), so a registered submodule never follows the machine into Execute — a tower
driven from FG_System.CurrentState would sit dark through all of production. The machine hands its
state down every scan through SetMachineIndication(State, Mode).
SetMachineIndication must be called before the machine's SUPER^.CyclicLogic(), which is what
calls this module's CyclicLogic. Otherwise the lock policy and the tower both act on last scan's
state.
| Condition | Lamp |
|---|---|
| not latched | dark |
| latched | solid |
latched and machine in Clearing
|
flashing |
The flashing case is the one that earns its keep. Clearing stalls until the safety chain is whole
again, so with two mushrooms on the cell an operator staring at a machine that will not clear needs
to know which one is still down. Solid-on-both says a mushroom is latched; flashing says that is
what is blocking you right now.
Phase comes from H_SignalTower.Flash (1 Hz, FlashTime 500 ms), re-exposed as IndicationFlash,
so the mushroom lamps, the red tower lamp and the panel's RESET button blink together rather than
against each other.
DriveEStopLamps() runs before SUPER^.CyclicLogic(), because FB_IlluminatedButton copies
Lamp to its coil inside its own CyclicLogic; setting Lamp after would put it a scan behind.
The decision lives in this module and not in FB_IlluminatedButton on purpose: a component must
not know which PackML state the machine is in. It exposes Lamp; the module that knows writes it.
Deliberate. NoStateTasksToComplete defaults TRUE and is re-armed on every state change, so each of
the base's transition states self-completes on the scan it is entered. An infrastructure module has
nothing to sequence, and a step chain here would only be one more thing for the machine's Resetting
to wait on.
Nine registered components. Forgetting one is silent — its CyclicLogic would simply never be
called, and a door would report neither closed nor locked for ever.
| Component | FB | Count |
|---|---|---|
B_SafetyDoor11..13, B_SafetyDoor21..23
|
FB_SafetyDoor |
6 |
SS_EStop1, SS_EStop2
|
FB_IlluminatedButton |
2 |
H_SignalTower |
FB_SignalTower |
1 |
22 DI + 20 DO. Six doors contribute two inputs and one coil each; the two mushrooms one input and one
lamp coil each; the tower four coils. The panel's own eight inputs and eight lamps belong to
MAIN.ControlSource_Panel, not to this module.
Each mushroom is one component carrying signal bit and lamp bit together — they are one device.
Both mushrooms are read normally closed — TRUE while healthy, FALSE while latched. That is how the real hardware is wired, and getting it the other way round has the worst failure mode available: a cut cable would read as "no emergency stop". So it is the sense every control platform reads against, and the twin inverts to match it rather than the reverse — the twin's
FB_ButtonreportsbValueTRUE while pressed, and the simulation layer negates it on the way into the process image. A platform that reads the twin directly, without that inversion, must invert on its own side instead; either way the mushroom input arrives NC.The consequence is deliberate: with no process image at all — the simulation not running, the fieldbus down — both inputs read 0, which under NC means latched, and the machine will not leave
Aborted. That is fail-safe, not a fault.How Beckhoff realises it is in
plc-io-exceptions.md.
-
transport-behaviour.md— the derived-not-stored rule this module follows -
fg-01-behaviour.md— the laser interlock, which is FG_01's own and not part ofSafetyOk -
state-lamp.md— the signal tower's state-to-colour mapping -
plc-io-exceptions.md— signals unlinked on purpose
Generated from DT_PSA_OPCV by _workflow/tools/build_wiki.py — 39 pages. Edit the source there; changes made here are overwritten.
Getting started
- Home
- Setup
- Using-The-Application
- How-It-Works
- PLC-Connectivity
- Engineering-Workflow
- Machine-Description
- Glossary
The machine
- Machine
- Machine-PLC-Symbols
- Machine-Provenance
- Machine-FG_01
- Machine-FG_02
- Machine-FG_03
- Machine-FG_04
- Machine-FG_05
- Machine-FG_System
- Machine-FG_Transport
Behaviour
- Behaviour-FG_01
- Behaviour-FG_02
- Behaviour-FG_03
- Behaviour-FG_04
- Behaviour-FG_05
- Behaviour-FG_System-Safety
- Behaviour-Gripper-Station-Reset
- Behaviour-State-Lamp
- Behaviour-Transport
Device types
- Device-Button
- Device-ControlBunker
- Device-Cylinder
- Device-DataReader
- Device-DrivePosition
- Device-DriveSimple
- Device-Lamp
- Device-LinkByte
- Device-Lock
- Device-PanelSampler
- Device-SensorBinary
- Device-SignalBinary
Control platforms
- Beckhoff TwinCAT 3
- Siemens TIA Portal — no wiki yet