FG_System — the safety contract

Published from _docs/reference/fg-system-safety.md — edit it there, not here. Changes made in the wiki are overwritten on the next sync.

Cell infrastructure: the enclosure, the six interlocked doors, the two emergency stops and the signal tower. It processes no parts. Written from the shipped ST; the PLC is master for behaviour.

Sources: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/01 FG_System/FG_System.TcPOU, Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/00 Machine/Machine.TcPOU.


The authority split inside safety

FG_System publishes two facts about the machinery and applies no policy to them.

Level Owns Members
FG_System the facts GuardsSecure, EmergencyStopActive
Machine the policy SafetyOk, EnforceSafety

Only the machine owns the PackML mode, and an equipment module that knows what ePMLUnitMode_Production implies has reached past its level. That is why the mode test lives in Machine.SafetyOk and not here.

Both facts are property getters, computed on every read — never stored flags. Same rule the transport stations follow for CanAccept and Occupied, for the same reason: a remembered readiness flag maintained in one state is stale in all the others.

EmergencyStopActive := SS_EStop1.Active OR SS_EStop2.Active;

GuardsSecure := B_SafetyDoor11.Secure AND ... AND B_SafetyDoor23.Secure;

Secure is shut AND locked. Closed alone is not enough.

The policy — Machine.SafetyOk

SafetyOk := NOT FG_System.EmergencyStopActive
        AND ( (_CurrentMode <> ePMLUnitMode_Production) OR FG_System.GuardsSecure );

Mode is the gate, and the two inputs are gated differently on purpose:

Input Acts in Why
Emergency stops every mode a mushroom is the one input that is never mode-dependent, and Manual is precisely the mode where somebody is inside the cell jogging a cylinder
Guard doors Production only, every state Maintenance and Manual ignore them — that is what those modes are for, and it is the only way into the cell, because the locks are commanded throughout Production

Machine.EnforceSafety calls AbortImmediate() whenever SafetyOk is false, except in Aborting, Aborted and Clearing:

Excluded state Why
Aborting / Aborted re-issuing AbortImmediate() every scan overwrites the command that would leave Aborted, so the machine could never recover. This is a deadlock, and the exclusion is the fix.
Clearing we are in Clearing because safety broke. Aborting out of it makes clearing impossible.

This is the path that disables FG_01's laser and retracts FG_04's press: the machine aborts, and the base Aborting carries the abort down to every registered submodule.

The lock policy

_DoorsRequestedLocked := (_MachineMode = ePMLUnitMode_Production);

Sealed in Production, free in Maintenance and Manual. That is the whole rule.

It is what makes "closed and locked in every Production state" reachable at all: the locks are already commanded at power-up, long before any reset, so a reset never has to wait for them.

The consequence is deliberate: an operator in Production cannot open a door at all. Getting into the cell means selecting Maintenance or Manual, which drops every lock.

A door has 3 s (LockTime) to confirm its lock before raising its own fault 1.

Indication

The tower shows the MACHINE's state, not this module's. Machine.Execute deliberately does not call SUPER^.Execute(), so a registered submodule never follows the machine into Execute — a tower driven from FG_System.CurrentState would sit dark through all of production. The machine hands its state down every scan through SetMachineIndication(State, Mode).

SetMachineIndication must be called before the machine's SUPER^.CyclicLogic(), which is what calls this module's CyclicLogic. Otherwise the lock policy and the tower both act on last scan's state.

The E-stop lamps

Condition Lamp
not latched dark
latched solid
latched and machine in Clearing flashing

The flashing case is the one that earns its keep. Clearing stalls until the safety chain is whole again, so with two mushrooms on the cell an operator staring at a machine that will not clear needs to know which one is still down. Solid-on-both says a mushroom is latched; flashing says that is what is blocking you right now.

Phase comes from H_SignalTower.Flash (1 Hz, FlashTime 500 ms), re-exposed as IndicationFlash, so the mushroom lamps, the red tower lamp and the panel's RESET button blink together rather than against each other.

DriveEStopLamps() runs before SUPER^.CyclicLogic(), because FB_IlluminatedButton copies Lamp to its coil inside its own CyclicLogic; setting Lamp after would put it a scan behind.

The decision lives in this module and not in FB_IlluminatedButton on purpose: a component must not know which PackML state the machine is in. It exposes Lamp; the module that knows writes it.

No state methods are overridden

Deliberate. NoStateTasksToComplete defaults TRUE and is re-armed on every state change, so each of the base's transition states self-completes on the scan it is entered. An infrastructure module has nothing to sequence, and a step chain here would only be one more thing for the machine's Resetting to wait on.

Components and I/O

Nine registered components. Forgetting one is silent — its CyclicLogic would simply never be called, and a door would report neither closed nor locked for ever.

Component FB Count
B_SafetyDoor11..13, B_SafetyDoor21..23 FB_SafetyDoor 6
SS_EStop1, SS_EStop2 FB_IlluminatedButton 2
H_SignalTower FB_SignalTower 1

22 DI + 20 DO. Six doors contribute two inputs and one coil each; the two mushrooms one input and one lamp coil each; the tower four coils. The panel's own eight inputs and eight lamps belong to MAIN.ControlSource_Panel, not to this module.

Each mushroom is one component carrying signal bit and lamp bit together — they are one device.

Both mushrooms are read normally closed — TRUE while healthy, FALSE while latched. That is how the real hardware is wired, and getting it the other way round has the worst failure mode available: a cut cable would read as "no emergency stop". So it is the sense every control platform reads against, and the twin inverts to match it rather than the reverse — the twin's FB_Button reports bValue TRUE while pressed, and the simulation layer negates it on the way into the process image. A platform that reads the twin directly, without that inversion, must invert on its own side instead; either way the mushroom input arrives NC.

The consequence is deliberate: with no process image at all — the simulation not running, the fieldbus down — both inputs read 0, which under NC means latched, and the machine will not leave Aborted. That is fail-safe, not a fault.

How Beckhoff realises it is in plc-io-exceptions.md.