Behaviour FG_05
Published from
_docs/reference/fg-05-behaviour.md— edit it there, not here. Changes made in the wiki are overwritten on the next sync.
Capping. Fits a cap from the bunker onto the part carried on the pallet. Written from the shipped ST; the PLC is master for behaviour.
Source: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/15 FG_05/FG_05.TcPOU.
The reset and resume model is in gripper-station-reset.md §5.
Ten symbols. Six cylinders, all FB_DoubleSolenoidFeedback.
| Group | Instances | FB |
|---|---|---|
| Cap handling unit |
Y_AxisX, Y_AxisZ1, Y_AxisZ2, Y_AxisR, Y_Gripper
|
FB_DoubleSolenoidFeedback |
B_Detect |
FB_DigitalSensor |
|
| Cap feed | Y_CapsSourceStopper |
FB_DoubleSolenoidFeedback |
Y_CapsSource (ControlBunker) |
FB_AbstractBunker |
|
B_Part |
FB_DigitalSensor |
|
| Vision | P_Camera |
FB_AbstractCamera |
The names are close enough to invite the mistake.
| Sensor | Where | Says |
|---|---|---|
B_Part |
on the feed | a cap has arrived at the pick position. Step 10 waits for it; once the gripper lifts a cap away it is reporting the next one |
B_Detect |
inside the jaws | this unit is carrying a cap. Steps 70 and 120 confirm against it, and it decides whether Resetting may open the gripper at all |
A cylinder limit cannot stand in for B_Detect: jaws that close on nothing reach .Extended sooner
than jaws that close on a cap, so .Extended is true either way.
Getting this wrong stalls the station permanently.
SequenceBunker.cs turns both bits on in OnEnable and off in OnDisable — it is a continuously
running feed, not a step. Driven from inside Execute it would stop between pallets, no cap would
ever be waiting when the next pallet arrived, and step 10 would block on B_Part for ever.
Y_CapsSource is therefore commanded from CyclicLogic, through the DriveBunker action, on mode
and state only.
Y_CapsSourceStopper is held, never indexed. An accumulating feed needs nothing more: the queue
pushes the next cap against the engaged stopper as soon as the gripper takes the one in front. It is
commanded to its blocking position and left there for the whole cycle.
It is commanded at Resetting step 0, before anything homes — not at the end of the reset. Its
de-energised position does not block, and the feed runs throughout Resetting and Idle, so a late
command would let caps spill past the pick position while the axes travel. Execute step 10
re-asserts it.
EXTENDED blocks the path. Settled 2026-08-22 by refactoring the device in the twin, and the PLC follows: both call sites are
Extend()and both waits are on.Extended.This is the opposite sense to the nine transport stoppers, where retracted holds — see the correction register in
transport-behaviour.md§6. That register was derived from theTS Index UnitandStopper Unitprefabs, and this device comes from neither, so the two facts do not contradict each other. Do not "correct" one to match the other.
P_Camera is mounted on the feed side but looks across at the pallet. The key it reads is the
assembly's CapsID, so the read answers "which cap does this assembly want", and the station
fits a cap only to an assembly of the type it is set up for. An empty pallet reads 0.
FG_01, FG_02 and FG_05 run the identical FB_AbstractCamera under the identical name over the
identical four status bits. The only difference between the three stations is which payload key their
twin reads and what value it has to be — here CapsID, expected 810. The comparison is made in
SIM_1's FB_Camera against a value set in this group's Mapping action, not in the control PLC;
the shared mechanism and the full datum table are in
fg-02-behaviour.md.
The read is first, and that placement is load-bearing.
Index05has already stopped and lifted the pallet before this group is triggered, so the assembly is in view from the first scan and there is nothing to wait for. Reading here means a NOK aborts before the gripper has taken anything — cap still in the feed, handling unit empty and home. Read after the pick instead and an abort strands a cap in the air above the part.
Execute, mode Production.
| Step | Action | Advances on | Timeout |
|---|---|---|---|
| 0 | derive entry from B_Detect; camera on, trigger cleared |
— | wrong park position → fault 4 |
| 10 |
Y_CapsSourceStopper.Extend (hold — extended blocks) |
B_Part.Active and SettleTimer 500 ms |
|
| 20 | wait for camera | P_Camera.Ready |
ReadyTimer 2 s → fault 2
|
| 30 | Trigger |
DeviceBusy or ResultValid
|
ShotTimer 3 s → fault 3
|
| 40 | read verdict |
ResultOK — else fault 1
|
ShotTimer → fault 3
|
| 50 | ClearTrigger |
— | |
| 60 |
Y_AxisZ2.Extend — down on the bunker side |
.Extended |
|
| 70 |
Y_Gripper.Extend — grip the cap |
.Extended and B_Detect.Active
|
GripTimer 500 ms → fault 5
|
| 80 |
Y_AxisZ2.Retract — lift clear |
.Retracted |
|
| 90 |
Y_AxisX.Extend — traverse to the pallet |
.Extended |
|
| 100 |
Y_AxisR.Extend — rotate, in the air and clear |
.Extended |
|
| 110 |
Y_AxisZ1.Extend — lower onto the part |
.Extended |
|
| 120 |
Y_Gripper.Retract — release |
.Retracted and NOT B_Detect.Active
|
ReleaseTimer 500 ms → fault 6
|
| 130 |
Y_AxisZ1.Retract — up, clear of the pallet |
.Retracted |
|
| 140 |
Y_AxisX.Retract — back over the feed |
.Retracted |
|
| 150 |
Y_AxisR.Retract — rotate home |
.Retracted |
|
| 160 | camera off, ChangeState(Complete)
|
— |
Where the cycle starts is derived, not remembered — step 0 reads B_Detect and the park position
rather than trusting a stored flag.
Both grip confirmations are two-part: the cylinder limit and the sensor. GripTimer and
ReleaseTimer are armed on the limit being reached, so the 500 ms budget covers the sensor
answering, not the stroke.
ST_FG_05_Capping_Status, published as HMI.Capping.FaultCode. Codes 1–3 are the camera's, shared
in shape with FG_01 and FG_02.
| Code | Meaning |
|---|---|
| 1 | this station does not cap that assembly (ResultOK false) |
| 2 | the camera never became Ready
|
| 3 | the shot never completed |
| 4 | started with a cap held by a unit that is not at its safe position |
| 5 | pick failed — jaws closed but B_Detect never confirmed |
| 6 | release failed — jaws opened but B_Detect never cleared |
An abort means Index05 never receives OperationDone and raises its own fault 3 on the operation
timeout. There is no reject station on this line.
No authored Safety section for this group. The cell chain (Machine.SafetyOk → AbortImmediate)
applies.
A de-energised double solenoid does not hold a gripped cap in the twin.
CyclicLogicre-asserts the grip every scan in every state butExecute.AbortingandStoppingleave the axes alone — not the grip.
-
gripper-station-reset.md— the reset model, safe positions, resume -
fg-03-behaviour.md— the same model with two arms -
fg-01-behaviour.md,fg-02-behaviour.md— the same camera protocol
Generated from DT_PSA_OPCV by _workflow/tools/build_wiki.py — 39 pages. Edit the source there; changes made here are overwritten.
Getting started
- Home
- Setup
- Using-The-Application
- How-It-Works
- PLC-Connectivity
- Engineering-Workflow
- Machine-Description
- Glossary
The machine
- Machine
- Machine-PLC-Symbols
- Machine-Provenance
- Machine-FG_01
- Machine-FG_02
- Machine-FG_03
- Machine-FG_04
- Machine-FG_05
- Machine-FG_System
- Machine-FG_Transport
Behaviour
- Behaviour-FG_01
- Behaviour-FG_02
- Behaviour-FG_03
- Behaviour-FG_04
- Behaviour-FG_05
- Behaviour-FG_System-Safety
- Behaviour-Gripper-Station-Reset
- Behaviour-State-Lamp
- Behaviour-Transport
Device types
- Device-Button
- Device-ControlBunker
- Device-Cylinder
- Device-DataReader
- Device-DrivePosition
- Device-DriveSimple
- Device-Lamp
- Device-LinkByte
- Device-Lock
- Device-PanelSampler
- Device-SensorBinary
- Device-SignalBinary
Control platforms
- Beckhoff TwinCAT 3
- Siemens TIA Portal — no wiki yet