FG_Transport — the behaviour contract

Published from _docs/reference/transport-behaviour.md — edit it there, not here. Changes made in the wiki are overwritten on the next sync.

How the transport ring actually sequences, interlocks and recovers. The PLC is master for behaviour, so this page is written from the shipped ST and every rule below can be pointed at a line of it.

This file is curated, not generated. No tool writes it. _docs/context/ is the opposite — derived from the twin and rebuilt wholesale — so the never-hand-edit rule applies there, not here. That is also why this page has to exist: anything under context/ that the build did not write is deleted, so behaviour knowledge cannot live there at all.

Source of every claim: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/10 FG_Transport/.


What this page is master of, and what it is not

Domain Master Where it lives
Structure — which devices exist, their PLC paths, device types, I/O, terminal channels the Unity twin the machine pages (generated)
Behaviour — sequences, handshake, interlocks, fault codes, reset the PLC this page

The MIL C# under Unity/Assets/Demo_1/Scripts/MIL/ is the twin's animation, not the behavioural contract. It still drives the twin acceptably standalone, but it implements the older design: no transfer latch, no check that the lift is at a level before running its carriage belt, and no reset path at all. Reading a handshake out of it today reproduces bugs that have been fixed.

The MIL's own vocabulary differs from the PLC's, and both names turn up in the scene. Use this table to read one as the other:

MIL (twin) PLC Note
Ready CanAccept derived, not stored
Busy Occupied derived; Busy is taken by FB_BaseFB and means something else
SendPayload() SendToNext → PayloadIncoming only a lift consumes it
Done (removed) the successor detects the pallet on its own sensor

The three invariants still hold and are still the reason the Index steps are ordered as they are; they are marked in the step table below.


1. The interface is derived, not assigned

Two properties are the whole readiness contract, and both are property getters computed on every read:

Occupied  := B_Detect.Active OR <transfer latch>;
CanAccept := <at home / blocking> AND NOT B_Detect.Active
                                 AND NOT <transfer latch>
                                 AND (_FaultCode = 0);
Unit CanAccept Occupied
Stopper FB_TransferStopper.TcPOU:429 :378
Index FB_TransferIndex.TcPOU:504 :434
Lift FB_TransferLift.TcPOU:201 (AtHome, derived from the carriage position — §3) :614

Why derived matters. The previous design stored _Ready and _Occupied and only maintained them inside Execute. Every other PackML state either wiped them or left them stale, which meant a reset that homed a lift with a pallet still aboard came back announcing an empty lift — and the upstream stopper released a second pallet into it. A getter cannot go stale, is correct in every state and every mode, and needs no second reset-only channel bolted alongside it.

There is no _Ready and no _Occupied variable anywhere in these three blocks. The step chains act; they do not define the interface.

One channel wires the ring, FG_Transport.TcPOU:423-433:

Lift01.NextCanAccept    := Stopper03.CanAccept;
Stopper03.NextCanAccept := Index01.CanAccept;
…
Stopper02.NextCanAccept := Lift01.CanAccept;

WireRing is the only place the chain order exists — no station knows what follows it, which is what lets one FB serve five index units. FG_Transport.TcPOU:414: "The wiring is the authority."

The Index station cycle

FB_TransferIndex.Execute, one chain for all five instances. The three invariants are marked where the code enforces them.

Step Action Advances on Fault
0 home: Y_Stopper.Retract (blocking), Y_Lift.Retract, handshake flags cleared —
10 confirm blocking position from the real switch limits 1 no block
20 idle and empty — the normal resting condition B_Detect
30 invariant 1 — Y_Lift.Extend while the stopper still blocks .Extended 2 lift did not raise
40 _ReadyForOperation := TRUE; wait for the group _OperationDone 3 group did not finish
50 invariant 2 — operation complete, so Y_Lift.Retract .Retracted 4 lift did not lower
60 invariant 3 — successor can accept; arm _Transferring NextCanAccept
70 Y_Stopper.Extend — release .Extended 5 no release
80 confirm the pallet actually left B_Exit rising edge 6 never reached exit

The unit clears _OperationDone itself once it sees it, so a group never has to reset anything. An Index with bypass set skips the call and dwells 1 s instead — useful for a station whose group does not exist yet.


2. The transfer latch — the only memory in the interface

A payload crossing a station boundary is invisible to sensors: a pallet drawn half onto a lift carriage has not reached B_Detect yet. That single case needs memory, and it is one plain BOOL per direction, initialising FALSE.

Unit Latch Armed at Cleared by
Stopper _Transferring (:61) commit to release, :247 rising edge of B_Exit, :185-188
Index _Transferring (:63) commit to release, :296 rising edge of B_Exit, :196-199
Lift _LoadingIn (:55) belt starts drawing in, :372 rising edge of B_Detect, :255-257
Lift _UnloadingOut (:56) commit to push off, :418 rising edge of B_Exit, :258-260

On the stopper and index the latch is SendToNext (:511, :608) — handing over and being mid-crossing are the same fact, so keeping them as one variable means they cannot disagree.

Three rules that are not obvious, and each cost a failure to learn

a. Clear on an edge, never a level. B_Exit may still be made by the previous pallet when the next release commits, which would clear the latch instantly and drop Occupied while a pallet was about to cross. R_TRIG instances at FB_TransferStopper.TcPOU:67, FB_TransferIndex.TcPOU:69, FB_TransferLift.TcPOU:62-63.

b. The witness may not be a live command. An earlier version qualified the clear with Y_Stopper.Extended (stopper) and M_Conveyor.RunForward/Backward (lift). Stopping and Aborting retract the cylinder and stop the belt immediately, so a stop during a crossing destroyed the very witness the clearing rule depended on — the latch could never go FALSE again, the station sat in Resetting for ever, and every predecessor with it. A sensor edge is the only witness a stop cannot erase.

c. Arm only when the ending sensor is clear. A latch armed while its ending sensor is already made will never see a rising edge and stays TRUE for ever. Hence B_Detect is tested first at the lift's Execute step 20 (:363-372), and _UnloadingOut := NOT B_Exit.Active at step 60 (:418).

d. Arm once, on the transition — never inside the waiting step. CyclicLogic clears the latch before the state method runs, so a step that re-asserts it every scan re-sets it on the very scan it was cleared. Both commits are on the transition into the pushing step, not inside it.


3. The lift — carriage axis and invariants

The carriage is a positioned axis

The lift carriage is driven by a servo axis (Y_Lift), not a cylinder. It has no end-position switches; where it stands is read from its position, measured from a reference.

Fact Value
Reference B_AxisMin, at the bottom of travel. Referencing sets the position there to 0 mm
Lower conveyor level 10 mm
Upper conveyor level 364 mm
At a level referenced and within ±1 mm of the level (AtLevel, :182)
Travel limits B_AxisMin and B_AxisMax. A made limit sensor forbids motion further in its own direction — in every state and mode — and always allows motion away from it (:288-289). Once referenced, software position limits of −2 / 370 mm apply as well

AtHome and AtFar are derived from the position every time they are read, like every other readiness fact here. Lift01 (ReverseDirection = FALSE) loads at the lower level and delivers to the upper; Lift02 is the mirror image. An axis that is not referenced is at no level — so until a reset has referenced it, the belt guard below stays shut and CanAccept stays FALSE. That is deliberate: an unreferenced position is a number, not a fact.

The Lift station cycle

FB_TransferLift.Execute, Production mode. Like the ring, it loops and never completes.

Step Action Advances on Fault
0 belt off. A pallet aboard → step 40; otherwise command the home level —
10 wait for the carriage at the home level and at rest AtHome 1 no home
20 pallet aboard → 40; announced by the predecessor → belt draws in, arm _LoadingIn PayloadIncoming
30 belt running inwards B_Detect 2 pallet never arrived aboard
40 settle 500 ms
50 command the far level — issued once move accepted 3 travel failed
55 wait for the carriage at the far level and at rest; then explicitly to 60 AtFar 3 travel failed
60 successor can accept; arm _UnloadingOut if B_Exit is clear NextCanAccept
70 belt pushes out B_Exit 4 pallet never left
80 belt off, back to 0 —

A level move is issued once and then watched, never re-issued every scan: the motion command is fire-and-forget, and the arrival test is the derived position, not the command's own status.

Steps are numbered by target, not by + 10, once the chain is not a plain decade. Step 55 used to advance with + 10 like its neighbours and landed on 65, a step that does not exist — the lift stood at the far level with the pallet aboard and the belt off, with no fault and no timeout.

The invariants

The carriage belt may only run while the carriage is at a level. Between levels the belt drives the pallet into a fixed edge. Enforced in CyclicLogic for every state and every mode — including Manual, where the operator jogs the belt by hand — at FB_TransferLift.TcPOU:279:

IF NOT (AtHome OR AtFar) THEN
    M_Conveyor.RunForward := FALSE;
    M_Conveyor.RunBackward := FALSE;
END_IF

A crossing can only start at a level, so a set latch is proof the carriage is in position. This is what makes Resetting safe: with a latch set it may run the belt without testing the axis; with no latch set nothing spans the gap, so the axis is free to move. The whole reset routing rests on it.

A second guard above it (:268-272) restricts the belt to Execute and Resetting. Note that guard runs before SUPER^.CyclicLogic(), so it does not merely veto the output for a scan — it erases the request the state method set on the previous scan, before the drive evaluates it. A state left out of that condition cannot move a conveyor at all, however plainly its code commands one. The same shape guards the main conveyors at FG_Transport.TcPOU:151.

A stop halts the carriage where it stands; an abort also takes the power off it. Stopping is orderly and Resetting resumes from wherever the carriage halted. Aborting — the safety chain's answer — must not rely on a servo holding position under power, so it removes the power once the axis is at rest, and does not wait for rest on an axis that is in error. Resetting powers the axis again before it moves it.


4. The reset model — accumulation

A reset re-establishes where the pallets are. It does not deliver anything.

  1. The group runs both main conveyors in the production direction for the whole of Resetting (FG_Transport.TcPOU:338).
  2. Every stopper and index blocks and never releases; the index also lowers its lift.
  3. Loose pallets travel up against the blocking stoppers and accumulate where a detect sensor can see them.
  4. Each station waits a fixed _AccumulateTime (5 s, FB_TransferStopper.TcPOU:86, FB_TransferIndex.TcPOU:99, FB_TransferLift.TcPOU:91), then clears its transfer latch and completes. After that, each station's state is simply what its sensor says.

Arming lines: FB_TransferStopper.TcPOU:494, FB_TransferIndex.TcPOU:594, FB_TransferLift.TcPOU:802.

The lift additionally finishes any interrupted crossing first — direction from the latch, belt only, axis untouched — then powers the axis, references it only if it has no reference, and moves to the home level (FB_TransferLift.Resetting, steps 30–40). The reference survives every PackML state, so in practice only the first reset after a power-up references; every later one goes straight to the home level.

The rule this produced: a reset must terminate on time and on its own actuators. Never on another unit, and never on an event that may not arrive.

Referencing is the one place a reset waits on a sensor, and it stays inside the rule: the sensor is the lift's own B_AxisMin, the decision to reference is a branch on the axis' own state sampled once, and the whole of it — powering, referencing — is bounded by one timeout (40 s, a full stroke at search speed). A reference sensor that never makes is fault 9, not a hang.

Both violations of that rule were shipped and both deadlocked:

  • The lift waited for its successor to report CanAccept before handing over during a reset. But a stopper never releases during a reset by design, so a stopper holding a pallet could never become free — the lift sat at the hand-over step with the whole group behind it. A reset must not depend on another unit doing something the reset forbids it from doing.
  • The stopper waited for an in-flight pallet to clear B_Exit before blocking, and the clearing rule needed a cylinder position that Stopping had already destroyed. See §2b.

_AccumulateTime must exceed the time a pallet needs to reach a stopper from mid-span. 5 s is a starting value, tuned against the twin, not a derived one.


5. Fault codes

Raised with ChangeState(E_PMLCommand.ePMLCommand_Hold), cleared in Clearing, published as HMI.Station.FaultCode. A non-zero code also forces CanAccept false, so a faulted station stops the ring behind it rather than accepting pallets it cannot move.

Code Stopper Index Lift
1 no block no home no home
2 no release lift did not raise pallet never arrived aboard
3 pallet never reached exit group did not finish travel failed
4 — lift did not lower pallet never left
5 — no release reset: pallet never came aboard
6 — pallet never reached exit reset: pallet never left
9 — — reset: carriage axis not referenced — timeout or axis error

Known drift: the ST_Transfer*_Status.TcDUT header comments still list the pre-reset code sets (ST_TransferStopper_Status and ST_TransferIndex_Status). The FB declarations are current; the DUT comments are not. Harmless — they are comments — but fix them when next in those files. ST_TransferLift_Status was brought up to date with the servo axis.

Lift codes 7 and 8 are declared in the FaultCode comment and never raised: they belonged to a reset that delivered the pallet, which deadlocked and was removed (§4).


6. Correction register — where the twin's prose is wrong

The PLC is master for behaviour, so these are corrections to the twin, recorded here until the authored entries are fixed in the scene.

Stopper polarity — nine authored Function entries are backwards.

RETRACTED (min) HOLDS THE PALLET. EXTENDING (max) RELEASES IT.

Asserted at FB_TransferStopper.TcPOU:20-22 and FB_TransferIndex.TcPOU:28, and confirmed by the twin's own geometry: Cylinder._limits = {0, 20} with axis _factor: -0.001 on the TS Stopper Typ 1 prefab, so max is the stopper down. The MIL agrees — SequenceTransferStopper.Idle() calls _stopper.MoveToMin() to block.

Two authoring sites, both prefab overrides; all nine exported entries inherited from them. Corrected 2026-08-19 in the prefabs, re-exported, and rebuilt into the digest:

Prefab Affects State
Unity/Assets/Demo_1/Prefabs/TS Index Unit.prefab Index01..05/Y_Stopper (5) fixed
Unity/Assets/Demo_1/Prefabs/Stopper Unit.prefab Stopper01..04/Y_Stopper (4) fixed

This entry is kept as a worked example of the correction path, not as an outstanding defect: the twin authored it one way, the PLC and the twin's own geometry said the other, and the PLC won. That is the authority split doing its job.

Related and correct — do not "fix" it: fg-01.md:103,111 says the FG_01 gates are "the opposite sense to the transport stoppers". Gate extended = closed = restrictive; stopper retracted = holding = restrictive. Genuinely opposite. That sentence only reads wrong while the stopper prose is wrong.

Two Role entries name the wrong successor. Lift01's prose says it feeds Index01; the wiring feeds Stopper03. Index05's says it releases towards Lift02; the wiring goes to Stopper04. Both skip the intervening stopper. The measured ring in machine.md shows the real order; FG_Transport.TcPOU:412-414 settles it — the wiring is the authority.


7. Reading order for a new group

  1. This page — the handshake contract and the reset model.
  2. The machine — the measured ring order and which Index serves which group.
  3. SPT framework — the framework, and the official build order that says to code Auto mode last.
  4. The group's own page — what its devices are.

Do not take a station handshake from a MIL coroutine. They describe the twin's animation, and the design they describe is the one this page replaced.