Behaviour FG_01
Published from
_docs/reference/fg-01-behaviour.md— edit it there, not here. Changes made in the wiki are overwritten on the next sync.
Identify and mark. Written from the shipped ST; the PLC is master for behaviour, so where this
disagrees with an authored Function entry in the twin, this wins.
Source: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/11 FG_01/FG_01.TcPOU.
Nine, all SPT components — no bare coils, no GVL.
| Instance | FB | Twin device |
|---|---|---|
Y_Gripper, Y_Platform, Y_ReaderWindow
|
FB_DoubleSolenoidFeedback |
Cylinder |
Y_Gate1, Y_Gate2
|
FB_SingleSolenoidFeedback |
Cylinder |
B_SafetyGate1, B_SafetyGate2
|
FB_DigitalSensor |
SensorBinary |
P_Camera |
FB_AbstractCamera |
DataReader |
Y_LaserMark |
FB_AbstractLightSource |
LinkByte |
P_Camera was P_Reader. Not a rename — the twin device became a DataReader with a real
vision-sensor protocol, so this station now drives the same FB as FG_02 over the same four status
bits. The old reader's single Result bit was an echo of its own trigger. Its function block and
DUTs were deleted 2026-08-22 once nothing referenced them.
This station does not verify its own mark.
P_Camerareads the payload keySerialNumber(expected 60, carried byAssembly Part 1); the laser writes a different datum,LaserMark, and FG_02 is what reads that back. The read happens after the laser fires, which invites the assumption that it is a verification. It is not — it is identification. A pallet with no part reads 0 and fails. The comparison itself lives inSIM_1'sFB_Camera, against a value set in that group'sMappingaction — seefg-02-behaviour.mdfor the shared mechanism and the datum table.
Y_Platform positions the laser head in service only and is never actuated by the cycle.
Execute, mode Production. Steps of 10; the whole chain is one CASE.
| Step | Action | Advances on | Timeout |
|---|---|---|---|
| 0 | laser off, camera on, trigger cleared | — | |
| 10 |
Y_Gate1.Extend + Y_Gate2.Extend together |
both .Extended and both B_SafetyGate*.Active
|
component travel, 3 s |
| 20 | Y_Gripper.Extend |
— | |
| 30 | settle |
ClampSettleTimer 500 ms, armed on Y_Gripper.Extended
|
|
| 40 | Y_LaserMark.Enable |
MarkTimer 1 s, then Disable
|
|
| 50 | Y_ReaderWindow.Extend |
— | |
| 60 | wait for camera | P_Camera.Ready |
ReadyTimer 2 s → fault 2
|
| 70 | P_Camera.Trigger |
DeviceBusy or ResultValid
|
ShotTimer 3 s → fault 3
|
| 80 | read verdict, latch _LastResultOK
|
ResultOK — else fault 1
|
ShotTimer → fault 3
|
| 90 |
ClearTrigger (tells the camera its verdict was read) |
— | |
| 100 | Y_ReaderWindow.Retract |
.Retracted |
|
| 110 | Y_Gripper.Retract |
.Retracted |
|
| 120 | both gates Retract
|
both .Retracted and both B_SafetyGate* clear |
|
| 130 | camera off, ChangeState(Complete)
|
— |
Two ordering rules that are load-bearing:
-
The camera is powered at step 0, not at the read. It has the whole gate-clamp-mark sequence to
come
Readyin, so the 2 s at step 60 is a grace period on top, not a cold-start budget. -
ReadyTimeris armed onY_ReaderWindow.Extended, not on the step. Step 50 extends and advances on the same scan, so step 60 waits on two things. Arming on the step alone would let a slow window burn the camera's budget and raise fault 2 — "the camera is not answering" — for a pneumatic fault. The window reports its own travel timeout.
Maintenance and Manual run no group sequence. Y_Platform and P_Camera stay reachable through
each component's own HMI control.
ST_FG_01_Identify_Status. Raised with AbortImmediate(), cleared in Clearing, published as
HMI.Identify.FaultCode.
| Code | Meaning |
|---|---|
| 1 | the part is not the one this station expects (ResultOK false) |
| 2 | the camera never became Ready
|
| 3 | the shot never completed |
A wrong serial number aborts the group. Index01 then never receives OperationDone and raises
its own fault 3 on the operation timeout — the same shape FG_02 uses on a NOK. There is no reject
station on this line, so a part that does not belong stops the pallet where it is and asks for a
human.
An entry check and an abort path, by design. The gates are closed and proven before the cycle is allowed to reach the laser, and they cannot open during it: the only step that opens them is step 120, eight steps after the burst has finished. A live per-scan permissive was considered and is deliberately not implemented.
What the code does:
-
On entry — step 10 will not advance until
Y_Gate1.Extended AND Y_Gate2.Extended AND B_SafetyGate1.Active AND B_SafetyGate2.Active. Closed for a gate is its extended limit, the opposite sense to a transport stopper. - By sequence position — the reader window is still retracted (shielding the optics) at step 40, because it does not open until step 50.
-
By abort — E-Stop in any mode, or a guard door in
Production, clearsMachine.SafetyOk;Machine.EnforceSafetycallsAbortImmediate(), and FG_01'sAbortingstep 0 callsY_LaserMark.Disable().
What the code does not do: re-check the gates on every scan of the 1 s burst.
Y_LaserMark.Enable() at step 40 carries no permissive term, and FB_AbstractLightSource.Enable()
is one line — OutputData.0 := TRUE;. This is accepted. FG_01 shuts the cell before it does
anything else, the gates are pneumatic cylinders held at their extended limit, and any real loss of
the safety chain reaches the laser through the abort path within a scan.
Note the FG_01 gates are not part of Machine.SafetyOk, which covers only the two E-stops and the
six enclosure doors. This interlock is this group's own, and the cell chain is what backs it.
| State | Leaves the station | Why |
|---|---|---|
Aborting |
laser off, camera off, window shielded, grip kept | releasing a clamped payload on abort would drop it |
Stopping |
laser off, camera off, window shielded, grip kept | so the cycle resumes after a reset without re-fixturing |
Resetting |
laser off, camera off, window shielded → grip released → gates opened | home is nothing energised; gates last, and only once the payload is free |
Clearing |
_FaultCode := 0, then every component Reset()
|
the fault clears by the act of clearing, not by the condition going away — a wrong part is still wrong after the camera stops reporting it |
Resetting terminates on its own cylinders and on nothing else, per the rule in
transport-behaviour.md §4.
Set in Initialize, in ms. They alarm on a jam; they do not pace the cycle.
| Component | Extend / Retract |
|---|---|
Y_Gripper, Y_ReaderWindow
|
2000 |
Y_Platform |
3000 |
Y_Gate1, Y_Gate2
|
3000 (longer stroke) |
-
transport-behaviour.md— the Index↔group handshake and the reset rule -
spt-framework.md— SPT V3.9 state machine and build order -
fg-02-behaviour.md— the same camera protocol, one station on
Generated from DT_PSA_OPCV by _workflow/tools/build_wiki.py — 39 pages. Edit the source there; changes made here are overwritten.
Getting started
- Home
- Setup
- Using-The-Application
- How-It-Works
- PLC-Connectivity
- Engineering-Workflow
- Machine-Description
- Glossary
The machine
- Machine
- Machine-PLC-Symbols
- Machine-Provenance
- Machine-FG_01
- Machine-FG_02
- Machine-FG_03
- Machine-FG_04
- Machine-FG_05
- Machine-FG_System
- Machine-FG_Transport
Behaviour
- Behaviour-FG_01
- Behaviour-FG_02
- Behaviour-FG_03
- Behaviour-FG_04
- Behaviour-FG_05
- Behaviour-FG_System-Safety
- Behaviour-Gripper-Station-Reset
- Behaviour-State-Lamp
- Behaviour-Transport
Device types
- Device-Button
- Device-ControlBunker
- Device-Cylinder
- Device-DataReader
- Device-DrivePosition
- Device-DriveSimple
- Device-Lamp
- Device-LinkByte
- Device-Lock
- Device-PanelSampler
- Device-SensorBinary
- Device-SignalBinary
Control platforms
- Beckhoff TwinCAT 3
- Siemens TIA Portal — no wiki yet