FG_01 — the behaviour contract

Published from _docs/reference/fg-01-behaviour.md — edit it there, not here. Changes made in the wiki are overwritten on the next sync.

Identify and mark. Written from the shipped ST; the PLC is master for behaviour, so where this disagrees with an authored Function entry in the twin, this wins.

Source: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/11 FG_01/FG_01.TcPOU.


Components

Nine, all SPT components — no bare coils, no GVL.

Instance FB Twin device
Y_Gripper, Y_Platform, Y_ReaderWindow FB_DoubleSolenoidFeedback Cylinder
Y_Gate1, Y_Gate2 FB_SingleSolenoidFeedback Cylinder
B_SafetyGate1, B_SafetyGate2 FB_DigitalSensor SensorBinary
P_Camera FB_AbstractCamera DataReader
Y_LaserMark FB_AbstractLightSource LinkByte

P_Camera was P_Reader. Not a rename — the twin device became a DataReader with a real vision-sensor protocol, so this station now drives the same FB as FG_02 over the same four status bits. The old reader's single Result bit was an echo of its own trigger. Its function block and DUTs were deleted 2026-08-22 once nothing referenced them.

This station does not verify its own mark. P_Camera reads the payload key SerialNumber (expected 60, carried by Assembly Part 1); the laser writes a different datum, LaserMark, and FG_02 is what reads that back. The read happens after the laser fires, which invites the assumption that it is a verification. It is not — it is identification. A pallet with no part reads 0 and fails. The comparison itself lives in SIM_1's FB_Camera, against a value set in that group's Mapping action — see fg-02-behaviour.md for the shared mechanism and the datum table.

Y_Platform positions the laser head in service only and is never actuated by the cycle.

Production cycle

Execute, mode Production. Steps of 10; the whole chain is one CASE.

Step Action Advances on Timeout
0 laser off, camera on, trigger cleared —
10 Y_Gate1.Extend + Y_Gate2.Extend together both .Extended and both B_SafetyGate*.Active component travel, 3 s
20 Y_Gripper.Extend —
30 settle ClampSettleTimer 500 ms, armed on Y_Gripper.Extended
40 Y_LaserMark.Enable MarkTimer 1 s, then Disable
50 Y_ReaderWindow.Extend —
60 wait for camera P_Camera.Ready ReadyTimer 2 s → fault 2
70 P_Camera.Trigger DeviceBusy or ResultValid ShotTimer 3 s → fault 3
80 read verdict, latch _LastResultOK ResultOK — else fault 1 ShotTimer → fault 3
90 ClearTrigger (tells the camera its verdict was read) —
100 Y_ReaderWindow.Retract .Retracted
110 Y_Gripper.Retract .Retracted
120 both gates Retract both .Retracted and both B_SafetyGate* clear
130 camera off, ChangeState(Complete) —

Two ordering rules that are load-bearing:

  • The camera is powered at step 0, not at the read. It has the whole gate-clamp-mark sequence to come Ready in, so the 2 s at step 60 is a grace period on top, not a cold-start budget.
  • ReadyTimer is armed on Y_ReaderWindow.Extended, not on the step. Step 50 extends and advances on the same scan, so step 60 waits on two things. Arming on the step alone would let a slow window burn the camera's budget and raise fault 2 — "the camera is not answering" — for a pneumatic fault. The window reports its own travel timeout.

Maintenance and Manual run no group sequence. Y_Platform and P_Camera stay reachable through each component's own HMI control.

Fault codes

ST_FG_01_Identify_Status. Raised with AbortImmediate(), cleared in Clearing, published as HMI.Identify.FaultCode.

Code Meaning
1 the part is not the one this station expects (ResultOK false)
2 the camera never became Ready
3 the shot never completed

A wrong serial number aborts the group. Index01 then never receives OperationDone and raises its own fault 3 on the operation timeout — the same shape FG_02 uses on a NOK. There is no reject station on this line, so a part that does not belong stops the pallet where it is and asks for a human.

Safety — the laser interlock

An entry check and an abort path, by design. The gates are closed and proven before the cycle is allowed to reach the laser, and they cannot open during it: the only step that opens them is step 120, eight steps after the burst has finished. A live per-scan permissive was considered and is deliberately not implemented.

What the code does:

  • On entry — step 10 will not advance until Y_Gate1.Extended AND Y_Gate2.Extended AND B_SafetyGate1.Active AND B_SafetyGate2.Active. Closed for a gate is its extended limit, the opposite sense to a transport stopper.
  • By sequence position — the reader window is still retracted (shielding the optics) at step 40, because it does not open until step 50.
  • By abort — E-Stop in any mode, or a guard door in Production, clears Machine.SafetyOk; Machine.EnforceSafety calls AbortImmediate(), and FG_01's Aborting step 0 calls Y_LaserMark.Disable().

What the code does not do: re-check the gates on every scan of the 1 s burst. Y_LaserMark.Enable() at step 40 carries no permissive term, and FB_AbstractLightSource.Enable() is one line — OutputData.0 := TRUE;. This is accepted. FG_01 shuts the cell before it does anything else, the gates are pneumatic cylinders held at their extended limit, and any real loss of the safety chain reaches the laser through the abort path within a scan.

Note the FG_01 gates are not part of Machine.SafetyOk, which covers only the two E-stops and the six enclosure doors. This interlock is this group's own, and the cell chain is what backs it.

Non-production states

State Leaves the station Why
Aborting laser off, camera off, window shielded, grip kept releasing a clamped payload on abort would drop it
Stopping laser off, camera off, window shielded, grip kept so the cycle resumes after a reset without re-fixturing
Resetting laser off, camera off, window shielded → grip released → gates opened home is nothing energised; gates last, and only once the payload is free
Clearing _FaultCode := 0, then every component Reset() the fault clears by the act of clearing, not by the condition going away — a wrong part is still wrong after the camera stops reporting it

Resetting terminates on its own cylinders and on nothing else, per the rule in transport-behaviour.md §4.

Travel timeouts

Set in Initialize, in ms. They alarm on a jam; they do not pace the cycle.

Component Extend / Retract
Y_Gripper, Y_ReaderWindow 2000
Y_Platform 3000
Y_Gate1, Y_Gate2 3000 (longer stroke)

Related