Negative Import Solar

bolagnaise edited this page Oct 18, 2026 · 3 revisions

Stop solar during negative import prices

Available from PowerSync v2.12.1418 for Home Assistant. The policy is off by default. It stops PV generation when the customer's current retail import price is below zero, allowing existing household loads and permitted battery charging to use paid grid imports. Zero export is a different operation: it can leave solar supplying the house and battery.

Enable Stop solar when the import price is negative in PowerSync's Curtailment settings. Existing battery dispatch, grid charging permissions, SOC limits, electrical limits and EV settings continue to determine consumption. The feature does not create extra loads or override those limits. Choosing to stop solar can forgo export income; this is an explicit import-price policy, not a calculation that selling solar is always less valuable.

Configuration fields

Setting Use
Stop solar when the import price is negative Opt in to stopping generation below zero retail import price. Off by default.
PV production controls (optional with supported native inverter) Select verified PV-only switches or production-limit numbers, or leave empty for a supported native control.
These controls cover all solar generation Enable only when every PV source is controlled, allowing the optimiser to plan without solar in negative-price intervals.
Controlled solar production power sensor (optional) Select power from the PV sources being controlled so fresh readings can confirm a production stop.
Retail import price sensor (optional) Supply a timestamped retail import interval when the provider cannot supply one directly.
Grid connected sensor (optional for Tesla) Required for non-Tesla systems. The selected sensor must provide fresh proof of utility-grid connection.

Controls and inverter coverage

Explicitly selected Home Assistant PV production controls work for any brand whose integration exposes a suitable control. Multiple controls can cover multiple inverters. A switch must mean on = PV enabled, off = PV stopped; a number must limit PV generation, accept zero, and have readable limits. Do not select an export limit, grid/islanding switch, battery dispatch setting, whole-hybrid shutdown switch, or a general load relay.

With no production entities selected, the following native controls are used:

Adapter Production operation Conditions and restore
Enphase DPEL production limiting with the existing Gateway or digital-input relay mode preserved Requires a readable baseline for the active mode and write access. Static Gateway mode uses a 0 W production limit; relay mode uses a zero-production relay table. Refreshes every 15 seconds. Restores the captured controls, preserving fresh installer metadata. No DER, profile or opposite-export-flag fallback.
Fronius SunSpec active output limit at 0% Separate PV inverter only. Saves enable, limit and reversion settings; does not introduce a reversion-to-100% timeout that could overwrite a prior cap. Fronius GEN24 storage entries require an independently verified PV-only entity instead.
Sungrow SG Run-mode register 5005=206 Explicitly known standalone SG model and readable run-mode baseline required. Restores the saved run mode; never stops an SH hybrid or changes its battery settings.
SolarEdge Active-power limit at 0% Separate PV topology; duplicate battery endpoint remains blocked. Restores the previous percentage, including non-default limits.
Zeversolar Percentage production limit at 0% Reads the actual advanced settings, saves enabled/mode/limit fields and restores them exactly.
Sigenergy PV maximum-power limit 40036, unsigned 32-bit zero DC PV only. Remote EMS must already be enabled in a mode where that register is effective (3–6). Never changes EMS mode, battery dispatch, grid export limits or third-party AC solar. Restores the original PV register even after the EMS mode changes.
FoxESS, Huawei, GoodWe, GoodWe entity bridge, SolaX, AlphaESS Explicit PV production entities Their existing PowerSync curtailment adapters control export/dispatch, not an established independent PV-only stop. They are not silently promoted to production controls.
Other brands Explicit PV production entities Requires a documented PV-only control exposed by the installed integration. A device without such a surface cannot be stopped by software through this feature.

Reading back a zero limit confirms a setting, not a physical effect. The new Solar Production Control sensor reports Stop Pending until a fresh controlled-PV power observation demonstrates a transition from producing over 100 W to at most 100 W. Without a suitable power sensor, or when solar was already zero at night, physical confirmation remains unknown. Command attempted, acknowledgement, device readback and physical convergence are separate attributes. restore_required identifies an outstanding ownership record; restore_pending identifies recovery currently awaiting completion.

From v2.12.1426, native Enphase control accepts mode-specific settings: static Gateway mode need not return a relay table, and relay mode need not return a static watt limit. PowerSync preserves the mode during stop and restore and can recover restore records saved by earlier releases. Missing active-mode settings still block commands. This compatibility correction does not establish that a particular gateway firmware, grid profile or microinverter combination physically enforces the limit; fresh controlled-PV readings remain necessary.

Price validity and recovery

A fresh utility-grid connection is required before stopping PV. Tesla uses its own current grid status. Other systems select Grid connected sensor: a binary sensor whose on state means utility-connected, or a sensor reporting Active, Connected, SystemGridConnected or On-Grid. Observations older than 90 seconds are rejected. A lost/unknown grid connection withdraws the stop and restores owned PV settings; it never suppresses backup solar from an old negative-price quote. Only an off-grid fallback session owned by PowerSync can be reconnected for this policy; a manual islanding state is not taken over.

Amber, Localvolts, Octopus and EPEX use finite, timestamped current retail import intervals. Feed-in prices are unnecessary for this policy. Forecast intervals, expired intervals, failed coordinator updates, NaN/infinity and raw AEMO/KWatch wholesale observations cannot authorize a new stop.

Other providers can supply the optional Retail import price sensor with startTime/endTime or valid_from/valid_to timezone-aware attributes. Supported units are c/kWh, ¢/kWh, p/kWh, $/kWh, AUD/kWh, EUR/kWh, GBP/kWh, €/kWh, and £/kWh. Currency-per-kWh values are converted to minor units. The value must be the customer's retail buy rate. An old scalar tariff or a sensor's change timestamp is not a current tariff interval.

At zero or a positive price, missing/expired price, disabled policy, changed controls or unload, PowerSync restores only the settings it still owns. The baseline is saved durably before the first write and retained after lost replies, partial writes and failed restores. Persistent device stops can remain in place while Home Assistant is offline; recovery needs Home Assistant and device connectivity. Restart loads that obligation before legacy AC controls can write. Failed commands use bounded exponential retry intervals. External changes are preserved and suspend this policy for the negative-price window. Manual inverter services restore the owned production settings first and suspend automatic stopping until a nonnegative price is observed.

Monitoring Mode blocks commands unless the existing explicit Allow curtailment control in Monitoring Mode permission is enabled. Permission transitions settle owned recovery before relinquishing control. Remaining export curtailment is re-evaluated after production recovery. Negative-import stopping never islands the Powerwall; optimizer off-grid projections exclude negative import slots.

Optimizer and evidence

Enable These controls cover all solar generation only when every PV source is covered. After current device controls have been confirmed, the optimizer can project zero PV during negative import slots. Mixed or unconfirmed sites retain their forecast. Raw solar forecasts are preserved, and deliberate production suppression is excluded from forecast learning and cloud nowcasting.

The capability matrix was checked against the adapter implementations at 0863c7d2e85ca46d8ff1272cc246685c28321cca (published v2.12.1417), then covered by focused control, recovery and routing regressions. These are source and simulated-control checks; they do not establish physical inverter behavior.

Primary references:

No customer inverter commands, Home Assistant installation, physical import increase or paid-import earnings were verified during implementation.

Verification boundary

Rung Implemented evidence Live proof
Eligibility Current retail interval, strict negative boundary, grid status, monitoring and capability regressions Simulated
Planned action Capability-scoped solar projection; negative import slots excluded from islanding Simulated
Effective action Manual/external ownership, shared control lock, expiry and unload/restart tests Simulated
Command boundary Native DPEL, Modbus and HTTP transports; explicitly selected HA production services Fake transports only
Acknowledgement Rejection, missing ACK, readback mismatch and retry cases Simulated
Hardware readback Exact prior/commanded register, DPEL or entity snapshots; partial-write recovery Simulated
Physical effect Fresh controlled-PV transition required; night/pre-command/missing observations remain unknown Not measured on hardware
Status Production sensor, existing AC status sensor and API keep unconfirmed stops pending Simulated

The first unproven live rung is an actual inverter command. Zero grid export, zero PV at night, an accepted request and a real production stop are competing explanations for superficially similar readings; the implementation keeps them separate. Implementation and verification issued no live device controls.